1.What is the maximum continuous load on a 15A breaker?
- A.15A
- B.12A (80%)✓
- C.10A
- D.13.5A
Why: CEC Rule 8-104: continuous loads limited to 80% of breaker rating. 15A × 0.80 = 12A. This prevents overheating of the breaker and wiring.
2.When running NMD90 through metal studs, what protection is required?
- A.None
- B.Approved bushings or grommets to protect cable from sharp edges✓
- C.Conduit only
- D.Tape around the cable
Why: NMD90 through metal studs requires approved bushings/grommets to protect cable insulation from the sharp edges of the stud knockouts.
3.A split receptacle requires what type of conductor?
- A.#14 AWG NMD90 2-conductor
- B.#14 AWG NMD90 3-conductor with bond✓
- C.#12 AWG 2-conductor
- D.Any standard 2-conductor
Why: Split receptacles need a 3-conductor cable (2 hots from different phases + neutral + bond) and the tab between the brass screws must be removed.
4.What is the ampacity of #14 AWG copper NMD90 at 30°C ambient?
Why: #14 AWG copper NMD90 is rated for 15A at 30°C ambient per CEC Table 2. Higher ambient temperatures require derating.
5.A bathroom exhaust fan and light on the same switch must be on a circuit rated for:
- A.The combined load of both devices✓
- B.The fan only
- C.The light only
- D.It doesn't matter
Why: The circuit and switch must be rated for the total combined load. Also verify the switch is rated for motor loads if controlling a fan motor.
6.When stripping NMD90, how much jacket should be removed inside a device box?
- A.As little as possible — just enough for connections✓
- B.150mm (6") minimum
- C.Remove all jacket inside the box
- D.300mm
Why: Remove only enough jacket to make connections. Excessive jacket removal exposes individual conductors unnecessarily. Leave at least 150mm of free conductor in the box.
7.Maximum box fill for a device box includes counting which items?
- A.Only conductors
- B.Conductors, clamps, devices, and ground wires✓
- C.Only devices
- D.Conductors and wire nuts
Why: Box fill counts: each conductor, internal clamps (1 count for all), each device/yoke (2 counts), and all grounds (1 count total). Wire nuts don't count.
8.A recessed luminaire (pot light) in an insulated ceiling must be:
- A.Any type, insulation doesn't matter
- B.IC-rated (Insulation Contact rated)✓
- C.Removed from the insulated area
- D.Covered with a fire-rated box only
Why: IC-rated luminaires are designed to be in direct contact with insulation without overheating. Non-IC fixtures require clearance from insulation.
17 more Branch Circuit Wiring questions inside
Plus a timed 309A exam simulator, spaced-repetition review of every question you get wrong, and an AI tutor you can ask “why?”.
Start free — 20 questions a day →RedSeal Prep Pro is an independent study tool. Practice questions are original content written in the style of the Certificate of Qualification and are not affiliated with the Red Seal Program, the Construction Electrician trade board, or any provincial certification body.